The electronic unit Model LC1 FL reduces the voltage and converts it to 5 VDC for operation of
reedswitches enhancing their life, above all ensuring operational safety. The LED's in the front
panel indicates Main Power Supply On, Pump Start and Stop conditions. The start/stop push
buttons in the front panel enables testing of the control unit and also manual start and stop. The
control unit has a Change over potential free relay output contact-hold on type. Contact change
over takes place between High and Low level only. Relay contacts are rated 5 Amps at 230 VAC.
Control action can be reversed at site by changing connections from NC to NO.
For certain applications where high and low level indications are required, 2 separate relay output
contacts are provided in the control unit-with LED indications for High, Low and Mains on